Fire Retardant conforms to BS 476 Part 6 & 7 - certified by CBRI Roorkee
Tested for 2 hours (Flame directly exposed on duct sheet)
Reduction in duct gauge construction or thickness
Reduction in duct reinforcement
Excellent Impact Resistance
Anti Corrosive & Anti Bacterial
Kitchen Exhaust Duct
Car Park Extract Duct
Smoke Extraction Duct
Stair Pressurization Duct
All the Smoke Extract/Car Park Extract/Kitchen Exhaust/Stair Pressurization Ducts shall be required to provide fire rating for fully functioning ductwork system in case of fire incident to provide a sufficient time for proper evacuation to building occupants. These ducts shall be coated with Fire Retardant Coating of minimum 700-micron (DFT) thickness to provide 2 hours Fire Rating. The Fire-Retardant Coating shall be tested as per requirements of BS 476: Part 6 ‘Class O’ and Part 7 ‘Class 1’. The Material shall be tested to confirm 2 hours fire rating with NIL flame spread when directly exposed to Flame.
Fire rating |
Certified as per BS 476 Part 6 and 7 from CBRI Roorkee |
2 hours fire performance |
Certified with National Test House (NTH). Flame exposed directly on coating (700 micron DFT) at 1200 deg C |
Impact Resistance |
No Loss of adhesion – IS 5585 – 120 Nm |
Corrosion Resistance |
ASTM D 1654 |
Artificial Weathering |
ASTM G 154 |
Pull off Strength |
ASTM D 4541 |
Specific Gravity |
1.38+/-0.02 |
Solid Content |
65% +/-2% |
Technical Coverage |
1 – 1.2 kg/m2 with 0.7 mm DFT on Duct Surface |
Application Temperature |
- 5 to 55 Deg C |
Shelf Life |
12 months from the date of manufacturing |